Standard Laboratory Facility Requirements
- Signs and Information
- Safety Equipment
- Signs and Information
- Restricted Access and Designated Areas
- Particularly hazardous substances.
- HIV and HBV research laboratories and production facilities.
- Biological agents that require Biosafety Level 2 or higher.
- Radioisotopes (Please contact the Radiation Safety Officer for requirements on these items).
- Storage Areas
- Particularly Hazardous Substance
- Corrosives
- Flammable/Combustible Liquids
- Flammable solids
- Oxidizers
- Perchloric Acid
- Biosafety Level 2 or higher
- Radioactives (please contact the Radiation Safety Officer for requirements on these items.)
- Safety Equipment
- Safety Showers
- Showers shall be located within 10 seconds where injurious corrosive materials are used.
- Showers must provide a 15 minute water supply at no less than 20 gallons per minute and must provide hands-free operation once activated.
- The location of the shower should be clearly marked, well lighted and free from obstacles, closed doorways, or turns.
- Eye Wash Facilities
- Eyewashes shall be located within 10 seconds where injurious corrosive materials are used.
- Eye wash facilities must provide the minimum of a 15 minute water supply at no less than 0.4 gallons per minute and must provide hands-free operation once activated.
- The location of the eyewash should be clearly marked, well lighted and free from obstacles, closed doorways, or turns.
- Ventilation Controls
- General (Dilution) Exhaust: a room or building-wide system, which brings in air from outside and ventilates within. Laboratory air must be continually replaced, preventing the increase of air concentration of toxic substances during the workday. General exhaust systems are not recommended for the use of most hazardous chemicals.
- Local Exhaust: a ventilated, enclosed workspace intended to capture, contain, and exhaust harmful or dangerous fumes, vapors, and particulate matter generated by procedures conducted with hazardous chemicals.
- Provisions for Local Ventilation
- Use with adequate ventilation.
- Avoid vapor inhalation.
- Use in a fume hood.
- Provide local exhaust ventilation.
- Make certain the hood you are using is appropriate for your work. (E.g.- Perchloric acid hoods are constructed of stainless steel and have internal wash-down capabilities; biological safety cabinets may be vented into the room and are not designed for chemical use.)
- Conduct all operations which may generate air contaminants at or above the appropriate PEL or TLV inside a fume hood.
- Keep all apparatus at least 6 inches back from the face of the hood and keep the slots in the hood baffle free of obstruction by apparatus or containers. Large equipment should be elevated at lesat two inches off the base of the fume hood, to allow for passage of air underneath the appartus.
- Do not use the fume hood as a waste disposal mechanism.
- Keep extraneous chemicals or apparatus out of the hood, as they will create air flow disturbances. Only material being used in an ongoing experiment should be kept in the fume hood.
- Keep paper and other light materials that might be drawn into the vent duct or fan out of the hood.
- Keep the hood sash completely closed at all times except when the hood is in use.
- Minimize foot traffic and other forms of potential air disturbance past the face of the hood.
- Do not have sources of ignition inside the hood when flammable liquids or gases are present.
- Make contingency plans in case of power failure or mechanical failure of the hood.
- Use the sash as a safety shield when boiling liquids or conducting an experiment with reacative materials.
- Periodically check the airflow in the hood using a continous monitoring device or another source of visible airflow indicator. If airflow has changed, contact the Chemical Hygiene Officer to schedule an inspection or Department of Facilities Services for a repair.